What is the optimum size of capillary tube in an air conditioner with 500w cooling capacity?
Generally
the diameter of the capillary tube varies from 0.6 mm-2.2mm, while length of
the capilary tube is around 0.3-4 m. The size of the capilary tube depedns on
type of rhe refrgerant used, suction pressure, delivery pressure, power
required by the compressor, and capacity of compressor.
The data is
being assumed
A R-12
system operates between 1.83 bar and 9.65 bar. The enthalpy at the begining of
compression (h1) is 181.94 k J/kg, while at the end of compression (h2) is 209.3 k J/kg,Total enthalpy of
refrigerant before evaporator= 74.77 kJ/kg; Obtain the length of capillary tube
of inner diameter 1.8 mm for 0.5kW compressor.
Compressor
work per unit area = w= h2-h1= 209.3-181.94= 27.4 kJ/kg;
Compressor
capacity for 0.5kW= mqcx3600=(0.5/27.4) 181.94-74.77)3600=
7040 kJ/kg
From log
graph, (variation of compressor capacity with the length of capillary tube for
different refrigerants), length of the capillary tube can approximately be
estimaed by knowing the diamter of the capillary tube. After conducting
experiment, exact size of the capillary tube can be determined.